Product introduction:
As our advance product, it ranks the highest level of the international cutout product after several improvements and optimizations. It is firm and strong in structure and accurate in fitting. And the interrupting current is up to 12.5kA.
Note: Technical datas and sketches are only for your reference. Such details in our contact prevail.
Model annotation:

Technical parameter:
Type | Rated voltage(kV) | Rated current(A) | 1min power frequency withstand voltage | lightning impulse withstand voltage | Rated breaking current (kA) | Insulator material |
Phase to phase and phase to ground(kV) | Between contacts(kV) | Phase to phase and phase to ground(kV) | Between contacts(kV) |
FCRW12-100/12.5 | 12 | 100 | 50 | 58 | 125 | 130 | 12.5 | Porcelain |
FCRW12-200/12.5 | 12 | 200 | 50 | 58 | 125 | 130 | 12.5 | Polymer |
FHRW12-100/12.5 | 12 | 100 | 50 | 58 | 125 | 130 | 12.5 | Porcelain |
FHRW12-200/12.5 | 12 | 200 | 50 | 58 | 125 | 130 | 12.5 | Polymer |
Appearance size: