Feeder Terminal Unit (Control Box)For Spring Actuated Circuit Breaker

GR-700

GR-700 intelligent feeder terminal unit, suitable for 10KV feeder section point or demarcation point, can switch between conventional protection and local feeder automation logic function through the function button on the panel, reducing the time and scope of power outage, and achieving line fault detection, isolation and power supply restoration of non-fault area.

Feeder Terminal Unit (Control Box)For Spring Actuated Circuit Breaker

GR-700

GR-700 intelligent feeder terminal unit, suitable for 10KV feeder section point or demarcation point, can switch between conventional protection and local feeder automation logic function through the function button on the panel, reducing the time and scope of power outage, and achieving line fault detection, isolation and power supply restoration of non-fault area.
Feeder Terminal Unit (Control Box)For Spring Actuated Circuit Breaker
Feeder Terminal Unit (Control Box)For Spring Actuated Circuit Breaker
Feeder Terminal Unit (Control Box)For Spring Actuated Circuit Breaker
Feeder Terminal Unit (Control Box)For Spring Actuated Circuit Breaker
Feeder Terminal Unit (Control Box)For Spring Actuated Circuit Breaker

Product introduction:

GR-700 intelligent feeder terminal unit, suitable for 10KV feeder section point or demarcation point, can switch between conventional protection and local feeder automation logic function through the function button on the panel, reducing the time and scope of power outage, and achieving line fault detection, isolation and power supply restoration of non-fault area.

It provides 4G/5G wireless communication, fiber optic Ethernet, dedicated line modem, intelligent wireless communication network and other communication modes to achieve fault information reporting and real-time uploading of line equipment information. It meets the standard IEC870-5-101/104, with serial and network DNP3.0 and other communication protocol libraries to achieve communication connections for various applications. It also equipped with parameter setting function to set or change local or remote control parameters. Its intelligent DC power supply to achieve dual power supply and smart management of backup lithium batteries.

 Note: Technical datas and sketches are only for your reference. Such details in our contact prevail.


Features

lThe modular pull-out structure making the box structure simple

lSuper capacitor as the working power source and lithium iron phosphate as the backup power source, such makes its effective service life up to 8 years

l5.5-inch color LCD display and high brightness, even for -40 ℃ low temperature area

lGraphical interface, easy to understand and operation

lConfiguration software for control logic design

lMultiple groups of parameters fixed value, the fixed value groups can be switched remotely or locally

lWith conventional protection and in-place feeder automation logic required by Chinese South Grid

lCommunication interface such as 4G/5G wireless interface, Ethernet/fiber optic interface, RS232


Model annotation:

image.png

Technical parameter:


NOItemGR-700
1Operation power supply27VDC
2Current input (nominal value)phase sequence:1V,zero sequence:0.2V
3Voltage input (nominal value)phase sequence:3.25V/√3,zero sequence:6.5V/3
4Current and voltage mearuring accuracyclass 0.5
5Active power,reactive power accuracyclass 1
6Telemetering9 Voltage channels, 4 current channels
7Remote signalling5 channels
8Remote control1 channel switch open and close
9AC current loop overload capacity1.2In,keep working;10In,1s
10AC voltage loop overload capacity1.2Un,keep working;2Un,1s
11SOE solution≤2ms
12Time keeping accuracyThe error is not longer than 1s for each 24 hours
13Input range of fault current10In
14Total error of fault current5%
15RS2322 Channels
16RJ45 Ethernet2 Channels
17CommunicationDL/T634.5101、DL/T634.5104  Communication protocol
18Terminal power consumptionwhole machine ≤8W
19Backup batteriesLithium iron phosphate Battery 25.6V/7AH
20Protection levelIP66
21Interface37-pin receptacle and plugs
22Dimension WxDxH420mm×174mm×660mm