24kV Intelligent Pole-Mounted Circuit Breaker (Magnetic Controlled)

ZNJWV1-24/Y630-20

24kV Intelligent pole-mounted magnetic controlled circuit breaker, three poles design, is mainly applicable for 24kV distribution network to interrupt the short circuit and earthing false, as demarcation switch, sectionalizer and connecting switch, also as outgoing switch in substation. Its breaking time is shorter than 10ms, which meets the demand of grade difference protection as high-speed switch. It can interconnect with the main station to realize distribution network automation, together with intelligent feeder terminal unit.

24kV Intelligent Pole-Mounted Circuit Breaker (Magnetic Controlled)

ZNJWV1-24/Y630-20

24kV Intelligent pole-mounted magnetic controlled circuit breaker, three poles design, is mainly applicable for 24kV distribution network to interrupt the short circuit and earthing false, as demarcation switch, sectionalizer and connecting switch, also as outgoing switch in substation. Its breaking time is shorter than 10ms, which meets the demand of grade difference protection as high-speed switch. It can interconnect with the main station to realize distribution network automation, together with intelligent feeder terminal unit.
24kV Intelligent Pole-Mounted Circuit Breaker (Magnetic Controlled)
24kV Intelligent Pole-Mounted Circuit Breaker (Magnetic Controlled)
24kV Intelligent Pole-Mounted Circuit Breaker (Magnetic Controlled)

Product introduction:

In the 24kV pole mounted magnetic controlled circuit breaker, we encapsulate the vacuum interrupter, main circuit live parts, high-accuracy voltage and current sensors, and high voltage pickup capacitors inside the cycloaliphatic-epoxy poles, based on decades of experience in solid insulation technology, eliminating all the partial discharge problems. The poles can pick up the voltage or current signals from power source side and secondary side at the same time, also the capacitor can power supply the intelligent electronic device (IED).

The three phases of the magnetic circuit breaker are driven by independent magnetic controlled mechanism respectively, which reduces dispersion, responding more timely and breaking more accurately. The breaking time is shorter than 10ms, which meets the demand of grade difference protection. The magnetic controlled circuit breaker is equipped with electrical latching and manual open handle, which latch electrically and manually the closing when the breaking handle is placed in the open position. 

Note: Technical datas and sketches are only for your reference. Such details in our contact prevail.


Model annotation:

型号注解.png


      Technical parameter:


NOItemUnitZNJWV1-12/Y630-20
1Interrupting medium-Vacuum
2Insulation medium-Solid   insulation
3Rated voltage kV12
4Rated frequencyHz50
5Rated currentA630
6Rated short-time withstand currentkA20
7Rated short circuit breaking currentkA20
8Rated peak withstand currentkA50
9Duration of rated short circuit s4
10Interrupting times of short circuit currenttimes≥30
11Rated operation sequence-O-0.3s-CO-180s-CO
12Rated lightning impulse withstand   voltage(1.2/50μs,peak)between   phases, phase to earth kV75
between interrupters kV85
13Rated power frequency short-time withstand   voltage (1minbetween   phases, phase to earth kV42
between interrupters kV48
14Partial   discharge of the whole breaker(CS, VS and pickup capacitor are included)Testing   voltagekV14.4
Partial discharge pC≤20
15Main resistanceμΩ≤80
16Mechanical operation lifetimeoperation≥20000
17Actuator type-Magnetic
18Operation type-Motor,with   manually opening and closing
19Operation voltage VDC220
20Closing timems≤60
21Opening timems≤15
22Synchronism in closing and openingms≤2 
23Current sensors inside the poleRated   current ratiophase   sequence600A/1V
Zero sequence20A/0.2V
Accurancyphase   sequencemetering   0.5s,Protection 5P10
Zero sequenceclass   1,Protection 10P10
Temperature range-40℃70℃
Implementation-low   power electro-magnetic
24Voltage sensors inside the poleRated   voltage ratiophase   sequence(10kV/√3)/(3.25V/√3)
Zero sequence(10kV/√3)/(6.5V/3)
Accurancyphase   sequenceclass   0.5
Zero sequenceclass   1
Temperature range-40℃~70℃
Implementation-capacitor   divider
Sampling type-power   side and load side voltage pickcup
25Capacitors   inside the polepower   supply-built-in   capacitor power supply
Installation -capacitor   power supply integrated in the pole
Single-phase rated output powerW10±10%
26Remote/Local   lockout-optional
27Re-close   function-N/M
28Manually   close lockout-N/M
29Closure protection level-not   lower than IP67
30Circuit breaker liftimeYear20